Lochinvar PRS3428 Switch, Air Pressure.
This comes complete with the mounting nuts and electrical female connector 1/4"

Used in the following models: ERN152, ERN302, ERN202, ERN402, ERN252, ERN151, ERN201, ERN251, ERN301, ERN401, ERL152, ERL302, ERL202, ERL402, ERL252, ERL151, ERL201, ERL251, ERL301, ERL401

Troubleshooting

INSTALLATION INSTRUCTION

FOR REPLACEMENT AIR PRESSURE SWITCH (PRS3428) FOR MODELS: ERN152 - ERN402 and ERL152 - ERL402

􏰁 WARNING

For an appliance already installed, you must turn off gas supply, turn off power and allow appliance to cool before proceeding. Components may be HOT! Failure to comply could result in severe personal injury, death, or substantial property damage.

List of kit components

Replacement procedure

1. Remove the wires from the Lochinvar air pressure switch as shown in.

2. Locate the two rubber hoses attached to the air pressure switch. Slide the tubing clips on the rubber hoses back and detach the rubber hoses from the air pressure switch.

3. Remove the air pressure switch.
4. Install the new parts4heating supplied air pressure switch.
5. Reinstall the two rubber hoses detached in Step 2

NOTE: Be sure to re-install the clear hose to the negative port and the gray hose to the positive port. Move the tubing clips back in place once the rubber hoses are reinstalled.

6. Reconnect the wiring disconnected in Step 1 to the new air pressure switch. Attach the female disconnect terminal (LUG7007) over the blade connector as shown in FIG 3. NOTE: Refer to the wiring diagram located inside the unit for proper wiring of the pressure switch.

7. Turn on the main electrical power and gas to the unit.
8. Reassemble the top outer jacket panel and resume operation.

Figure 2 Remove air pressure switch

DISCONNECT WIRES

REMOVE AIR PRESSURE SWITCH

DISCONNECT WIRES

REMOVE AIR PRESSURE SWITCH

Kit Part Number

Lochinvar PRS3428

Recommended tools:
  • 1/4" Nut Driver

  • 5/16" Nut Driver

  • Needle Nose Pliers

    To gain access to the interior of the appliance

    1. Turn OFF the main electrical power to the appliance.

    2. Turn OFF the main manual gas shutoff to the appliance.

    3. Remove the top outer jacket panel.

4. Follow the procedures in this instruction sheet to replace the air pressure switch.

Figure 1 Remove top outer jacket panel of the Lochinvar Energy Rite

REMOVE TOP OUTER JACKET PANEL

SLIDE TUBING CLIPS BACK DISCONNECT TUBING

Figure 3 Replace air pressure switch

RECONNECT WIRING AND ATTACH TERMINAL (LUG7007)

RECONNECT TUBING (2)


Share your knowledge of this product with other customers... Be the first to write a review


Reznor 5145 Pilot Tubing, 22 in. Length $37.95
RAYPAK 005503F PC BOARD INDUCED DRAFT-KIT $230.72
Teledyne Laars HH 2200 HH 2450 PH 2200 PH 2450 VW 2200 VW 2450 IW 2200 IW 2450 AP 2200 AP 2450 MT 2200 20005802 Tile Cover (qty 2), 2450I/2200E $54.13
Triangle Tube PSJKT01B Base Panel (60/110) $315.39
Lochinvar FIB2134 , 100145470 FRONT PANEL, 751 $227.12
Smith 51180 Intermittent Ignition Module, S8610M $124.84
Hayward CZXCON3645 Contactor $229.74
Lochinvar GTP30002 TEMPERATURE and PRESSURE GAUGE; OPTIONAL $178.41
Lochinvar ORF2004 , 100164071 ORIFICE MAIN BURNER, NAT. $75.27