Fenwal 35-679751-565 Ignition Control 24 VAC Proven HSI W/Blower Relay
SPECIFICATIONS | INPUT VOLTAGES | DESCRIPTION | | Control | 18 to 30 VAC, 400mAmax (not including gas valve) | | Line | 24/120/240 VAC (L1 & L2 only, voltage depends on model) | | Thermostat | 18 to 30 VAC 30mAmax (incl. Gas Valve) | | Pressure Switch | 18 to 30 VAC 25mAmax | | Hot Surface Element | 24/120/240 VAC 5Amax | | Output Ratings | | | Inducer Fan | Relay: 15Amax or 1/3HP @ 120 or 240 VAC | | Hot Surface Element | 5.0Amax @ 24, 120 or 240 VAC | | Gas Valve Rating | 5.0Amax @ 24 VAC | | Lockout & Pre-Purge Indicators | 1.0Amax @ 24 VAC | | Operating Temperature | -40F to +165F (-40C to +73C) | | Flame Sensitivity | 4.0mAminimum | | Flame Failure Response Time | 0.8 seconds max | | Types of Gas | Natural, LP, or manufactured | | Ignitor | 24 VAC, 120 VAC, or 240 VAC mini-ignitors and silicon carbide ignitors depending on model | | Enclosure | Gray (Noryl N-190) | | Moisture Resistance | Conformal coated to operate non-condensing to 95% R.H. Care must be taken to protect module from direct exposure to water | | Size with enclosure | See Figures 6 & 7 | | Weight | 8oz including options and cover | CONTROL CONFIGURATION | Other Features | Manual Reset (Standard Includes Indicators and Inducers) | Proven Pressure Switch, Full Time Power, Termination | Full Time Power, Mate-N-Lock, Local Reset Button | Dwell Time | 20 Seconds | Tries For Ignition | 15 Prepurge, 15 Interpurge, 0 Postpurge | Tries For Ignition | Single Try - Remote Sense. Recycle On Flame Loss | Purge Timing | 15 Prepurge, 15 Interpurge, 30 Postpurge (Full Time Power) | Proving Current (Amps) | 3.1 | Trial for Ignition | 10 Seconds
|
|
|
 |
 |
 |
 |

|