| Input Power | Control: 18-30 VAC 50/60 Hz (Class 2 Transformer) |
| Input Current Drain | 300 mA@24 VAC with gas and pilot relays energized (Control only) |
| Main Gas Valve | 2.0Amax (continuous) |
| Pilot Gas Valve | 2.0Amax (continuous) |
| Operating Temperature | -40F to +176F (-40C to +80C) |
| Storage Temperature | -40F to +185F (-40C to +85C) |
| Flame Sensitivity | 0.7 uAminimum |
| Flame Failure Response Time | 0.8 seconds maximum |
| Types of Gases | Natural, LP, or manufactured |
| Spark Rate | Line frequency (50/60 sparks/sec) |
| Size (LxWxH) | 5.69 x 3.94 x 1.87 inches (with cover) 14.45 x 10.01 x 4.75 cm (with cover) |
| Weight | 8 ounces (nominal) 224 grams (nominal) |
| Moisture Resistance | Conformal coated to operate non-condensing to 95% R.H. Care must be taken to protect module from direct exposure to water |
| Tries for Ignition | One or three try versions available |
| Trial for Ignition Periods | 15, 30, 60, 90 seconds available |
| Prepurge Timings | None, 15, 30, 45 seconds or 4 minutes available |
| Interpurge Timings | None, 15, 30, 45 seconds, or 4 minutes available |